Skip to content

Operator task guide

NVIDIA Xid 79, 94, 119, and 149 triage playbook

Xid 79 (GPU has fallen off the bus), Xid 94 (contained uncorrectable ECC), Xid 119 (GSP RPC timeout), and Xid 149 (Blackwell NETIR link-down) are the four most common hardware and firmware Xids on modern H100, H200, and B200 clusters, yet each demands a different recovery path.

Never blindly reset or RMA a GPU on a single Xid number. Preserve GPU UUID, serial, PCI bus ID, dmesg context, and BMC power/thermal records first: Xid 119 is often a driver/GSP firmware bug, Xid 94 contains memory faults to one process, Xid 79 can come from a bad riser/PSU, and Xid 149 requires inspecting both NVLink endpoints.

Reviewed . Reference guidance is not a diagnosis of your workload.

Step-by-step method

  1. 1

    Capture complete Xid lines, timestamps, and GPU UUIDs before rebooting

    Driver and PCIe kernel evidence disappears on reboot. Dump dmesg, nvidia-smi identity, and nvidia-bug-report.sh while the fault state is intact.

    dmesg -T | grep -iE 'NVRM: Xid|AER|PCIe|nvlink'
    nvidia-smi --query-gpu=index,uuid,serial,pci.bus_id,driver_version --format=csv
  2. 2

    Branch by exact Xid code: 79 vs 94 vs 119 vs 149

    Match the observed code to its NVIDIA classification: Xid 79 needs PCIe/power/thermal and card-vs-slot evidence; Xid 94 kills only the faulting process while checking row-remapper headroom; Xid 119 indicates GSP firmware stall fixed in newer driver releases; Xid 149 requires full NETIR subcode and peer port counters.

    nvidia-smi -q -d ECC,ROW_REMAPPER
    nvidia-smi nvlink -e
  3. 3

    Separate shared-node events from single-GPU defects

    If multiple GPUs on one host emitted Xid 79 or Xid 149 within milliseconds, investigate baseboard power delivery, liquid cooling loops, PCIe switches, or NVSwitch trays before pulling individual GPUs.

  4. 4

    Run post-recovery workload validation before clearing the node

    After an operator-approved reset or driver update, run dcgmi diag and a production-shaped test job while verifying the same Xid does not return.

Xid 79, 94, 119, and 149 comparison

Signals, meanings and actions for nvidia xid 79, 94, 119, and 149 triage playbook.
SignalWhat it meansNext action
Xid 79: GPU has fallen off the busPCIe communication to GPU lost (power, thermal, riser/slot, or card).Check BMC power/thermal and PCIe AER logs; verify fault follows card before RMA.
Xid 94: Contained ECC errorUncorrectable ECC isolated to one faulting process context.Restart affected job, inspect ROW_REMAPPER pending/failure state, watch recurrence.
Xid 119: GSP RPC timeoutGPU System Processor firmware RPC stalled.Compare driver version against NVIDIA release notes; reset/upgrade driver before RMA.
Xid 149 (e.g., 149.4): Blackwell NETIR link eventNVLink 5 / NETIR transport error on GPU or peer switch.Preserve exact NETIR subcode and check NVLink error counters on both endpoints.

Evidence checklist

  • Exact dmesg NVRM: Xid lines including subcodes (such as 149.4)
  • GPU UUID, serial number, PCI bus ID, and driver/VBIOS version
  • nvidia-smi -q -d ECC,ROW_REMAPPER and nvlink -e counters
  • BMC / IPMI power, PSU, and thermal logs from the same UTC window
  • Whether adjacent GPUs on the same baseboard logged concurrent Xids

Common mistakes

Filing an immediate RMA for Xid 119 without checking driver release notes

GSP RPC timeouts are heavily driver-version dependent and frequently resolve with NVIDIA driver updates.

Confusing Xid 94 (contained) with Xid 95 (uncontained)

Xid 94 isolates corruption to the killed process; Xid 95 compromises wider GPU state and requires node drain.

Rebooting first and collecting logs afterward

Volatile dmesg and AER registers reset on reboot, leaving OEMs without actionable RMA evidence.

Frequently asked questions

What causes NVIDIA Xid 79 (GPU has fallen off the bus)?

Xid 79 means the kernel driver lost PCIe reachability to the GPU. Common root causes include PSU rail droop under high load, thermal shutdown, damaged PCIe risers or slots, or a failing GPU board.

What is the difference between Xid 94 and Xid 95?

Xid 94 is a Contained ECC error where hardware isolated the memory fault to one process. Xid 95 is an Uncontained ECC error that affects broader device state, requiring node drain and checkpoint rollback.

Is Xid 119 a hardware failure?

Usually not on its own. Xid 119 is a GSP (GPU System Processor) firmware RPC timeout, often tied to specific R535/R550/R570/R580 driver bugs rather than broken silicon.

What does Xid 149.4 mean on NVIDIA B200 / GB200?

Xid 149 subcodes report Blackwell NVLink 5 / NETIR link-down and bit-error events. Capture the exact subcode and compare nvlink error counters on both link endpoints before replacing cables or GPUs.

Live diagnosis, no signup

Upload your GPU log. Find what happened first.

Get the likely cause, supporting evidence, and next safe steps with the same cloud reasoning used by paid plans. A crash the engine recognizes is answered in seconds, then checked by an independent AI review that updates this page when it finishes. A crash it does not recognize waits for the AI's own answer, which can take a few minutes. No account, card, or installation. Logs are masked at Denpex API ingress and are not saved to account history.

Before uploading, review cloud data handling and local options.

training_logs.txt
No log to hand? Try one:

Upload your log file. Large files are processed in your browser. Only selected evidence is submitted when you run diagnosis.

3 free cloud diagnoses per day

Try Denpex for 30 days. FREE.

No credit card. No automatic subscription. See whether Denpex helps with an incident you already understand.

Start your free 30-day Team evaluation

Up to 50 diagnoses a day for 30 days. Verify your work email to activate an eligible company evaluation, then replay a resolved incident and compare the evidence and next steps with your team's confirmed cause.

Use your company email, for example alex@yourcompany.com.

Who qualifies?

Company email domains activate the free 30-day Team evaluation (up to 50 diagnoses a day) after an email and domain check, whatever mail provider you use. If we cannot verify your domain automatically, support reviews it: write to support@denpex.com. Free local diagnosis in the editor extension needs no account.

Using a personal email (Gmail, Outlook, Naver, QQ) or solo cluster? Create a free $0 account (no work email required) to save 7-day history and unlock AI fallback, or send a cluster crash log for a live walkthrough.

Apply the method to your incident

Use the three free diagnoses to review your error and relevant evidence. Keep reference guidance separate from the cause and recovery status of your own workload.

Diagnose your incident